Skip to main content
·Technical

Technical Guide for Solaronics Industrial Heating Projects

From measurement to running system in 5 steps: measure, size, select model, mounting, commissioning. For engineers and installers on a first project.

From space measurement to running system in five steps. This guide covers the full workflow: space parameter measurement, required output sizing, model selection, key mounting requirements, and a commissioning protocol with a startup fault-finding table.

Step 1: Measure the Space

Measure or assess four parameters before selecting any appliance. Without them, every model proposal rests on assumptions rather than site data.

Parameter Unit Note
Heated zone floor area Heated zone only. Exclude unheated areas if the space is zoned
Ceiling height m At the lowest point for pitched or mono-pitch roofs
Thermal envelope insulation class Uninsulated closed shed / roof only insulated / traditional construction / well insulated
Entrance openings type + frequency Required for air curtain sizing only

Step 2: Determine Required Total Output

Reference values for a 1,000 m² space at 7 m ceiling height (from Solaronics sizing curves):

Insulation class Hot air. Total output Radiation. Total output
Uninsulated closed shed ~350 kW ~200 kW
Roof only insulated ~280 kW ~150 kW
Traditional construction ~200 kW ~110 kW
Well insulated ~50 kW ~55 kW

The advantage of radiation over hot air is greatest in poorly insulated spaces above 5 m and disappears at good insulation levels. For the physics behind the difference: Radiant Plates vs. Unit Heaters.

Site-specific sizing is prepared by the Solaronics technical team on receipt of the Step 1 parameters.

Step 3: Select the Model

MC Eco3 Condensing Unit Heater

Model Input kW Nominal output kW Min. output kW Air flow m³/h
MC35 Eco3 36 34 19 4,250
MC45 Eco3 46 43 24 5,250
MC60 Eco3 61 56 32 7,000
MC80 Eco3 80 73 42 9,000

Seasonal efficiency: above 78%. Thermal efficiency at nominal output: 92%; at minimum output: 95%. NOx: below 70 mg/kWh.

SRII Radiant Plate

Output per plate: 6.2–25.7 kW depending on model. For a typical 110 kW total output requirement (traditional construction, 1,000 m², 7 m ceiling from Step 2): 4–6 units depending on selected model. Mounting height: 4–15 m. Gas connection: 1/2" BSP.

Step 4: Mounting Requirements

Requirement SRII MC Eco3 / MH / MV / CA
Fixing 4 × Ø7 mm bores in ceiling structure; structural engineer to confirm load Wall brackets or suspended ceiling; load stated in datasheet
Gas connection 1/2" BSP; G20=20 mbar, G25=25 mbar, G31=37 mbar G3/4" BSP; same pressures
Electrical supply 230 V / 50 Hz, single phase, 10 A 230 V / 50 Hz, 10–16 A by model
Thermostat input 230 V contact signal 230 V contact signal
Minimum mounting height 4 m By series table (3–10 m)

Safety clearances to combustibles are stated in the technical datasheet for each model. For full installation instructions: Installation Instructions.

Step 5: Commissioning and Startup Fault-Finding

  1. Measure gas pressure at the appliance connection (not at the building entry meter).
  2. Check all fittings for leaks with foam solution or a gas detector.
  3. Apply electrical power; wait for control unit self-test to complete (30–60 s).
  4. Set thermostat and verify ignition; red or orange flame indicates insufficient combustion air. Check air flow and filter condition.
  5. After 10 minutes: measure temperature profile in working zone and compare to design value.

Common Startup Faults

Symptom Likely cause Action
No ignition, no controller fault Low gas pressure at connection Measure pressure with manometer; check pressure regulator
Unstable flame, shutdown Wrong gas category (e.g. G20 injectors on G25 supply) Check appliance label and gas category at connection
Appliance runs, space below design temperature Undersized total output or incorrect zone layout Check temperature profile by zone; compare against Step 2 sizing
High housing temperature, thermal cutout trips Blocked filter or insufficient mounting height Check filter condition; verify mounting height against datasheet
Power and gas OK, no appliance response Thermostat wiring fault (half-contact) Check contact signal at control unit terminals

After first commissioning and first periodic check: Maintenance and Regular Service.

[CTA: Request project-specific sizing → /povprasevanje?source=informacije/tehnicni-vodnik]

Question?

Technical engineer replies within 24 hours.